Three Phase Line Conditioning Reactors
Epco's transformers are rugged layer wound constructed with high quality materials to meet the safety and reliability demands of the domestic/international marketplace.

- Three Phase Line Conditioning Reactor
Applications: SCR controls and drives to minimize line notching, protect sensitive electronics (such as SCRS and rectifiers) from current surges, filter line disturbances in multiple drive systems, help stabilize line conditions in the absence of isolation transformers.
Working Volts : 600V, 60 Hz
Overload Rating : 150% for two minutes
: UL Insulaton System Class H 180º C
NEMA: Enclosed units available upon request.
Line Impedance: 3% @ 480V, 5% @ 240 V
EP # |
Line Amps AC |
Inductance uH |
Max HP 240V |
Max HP 480V |
Size H x W x D |
Weight |
|---|---|---|---|---|---|---|
7745 |
6 |
5000 |
- |
3 |
6 x 5 x 5 |
6 LB. |
7746 |
10 |
2750 |
2 |
5 |
6 x 7 x 6 |
7 LB. |
7747 |
15 |
1500 |
3 |
7.5 |
6 x 7 x 6 |
7 LB. |
7748 |
25 |
900 |
5 |
10 |
7x 9 x 6 |
15 LB. |
7749 |
35 |
750 |
7.5 |
15 |
8 x 8 x 6 |
15 LB. |
7750 |
50 |
500 |
10 |
25 |
9 x 10 x 7 |
25 LB. |
7751 |
75 |
375 |
15 |
40 |
11 x 11 x 9 |
50 LB. |
7752 |
100 |
275 |
25 |
60 |
12 x 12 x 14 |
52 LB. |
7753 |
130 |
200 |
30 |
75 |
12 x 13 x 14 |
56 LB. |
7754 |
160 |
175 |
40 |
100 |
14 x 15 x 12 |
62 LB. |
7755 |
250 |
100 |
75 |
150 |
16 x 14 x 12 |
123 LB. |
7756 |
300 |
80 |
100 |
200 |
Consult Factory
|
|
7757 |
480 |
50 |
150 |
300 |
Consult Factory |
|
EPCO Products, Inc.
Box N, 63 Railroad Ave., Wallkill, NY 12589 | T 845-895-2033 F 845-895-2279
Email: sales@epcoinc.com
Box N, 63 Railroad Ave., Wallkill, NY 12589 | T 845-895-2033 F 845-895-2279